AHU / FCU Sizing

Enter an air handler or fan-coil unit's cooling capacity to get the chilled-water coil flow and pipe size, the supply airflow, and the round / spiral supply duct diameter — the duct we fabricate in-house. Related: chiller plant pipe sizing.

Typical 5–6 °C across the coil.
Room minus off-coil supply temperature (typ. 9–12 °C).
Sensible ÷ total cooling; ~0.75–0.9 for comfort cooling.
Typical 5–8 m/s for commercial supply ducts.
Advanced limits (water pipe)
Unit capacity
Chilled water flow
Supply airflow
ItemQuantitySizeVelocity

Method: coil flow = capacity ÷ (4.187 × ΔTwater); supply airflow = (capacity × SHR) ÷ (1.2 × 1.005 × ΔTair); round duct Ø from airflow at the target velocity (rounded to 25 mm). Pipe to ASHRAE / SNI limits (Hazen-Williams). Indicative only — confirm against the selected unit's catalogue data. We fabricate the matching square & spiral duct in-house — get a quote.